Cycloalkane Based Transformer Oil T-20 Insulating Oil

The product should have a high compressive strength, the minimum compressive strength should be 30KV (kilovolt). No chemical salts and other dirt, no sulphur content, so as not to corrode the copper metal. The oil quality is uniform and consistent.


Product Details

Product Details:Cycloalkane Based Transformer Oil T-20

The insulating oil has very high insulation resistance and breakdown voltage, which can effectively prevent the abnormal flow of current inside the equipment and ensure the safe operation of the equipment.


Cycloalkane Based Transformer Oil T-20


PARAMETER

Sports Event

Quality Indicators

measured value

Test Methods

Functional characteristics

Pour Point/°C

-30

-38.8

ISO 3016

Kinematic viscosity (40℃)/(m㎡/s)

≯12

9.20

 

ISO 3104

Kinematic viscosity (-10°C)/(mm²/s)

≯1800

1089

ISO 3104

Water content/(mg/kg)

≯30/40

7.5

IEC 60814

Breakdown voltage/kV (untreated oil)

≮30

63.0

IEC 60156

Density (20°C)/(g/ml)

≯895

886

ISO 12185

Dielectric loss factor (90°C)

≯0.005

0.00045

IEC 60247

Refining/stabilizing properties

exterior condition

Clear and transparent, free of sediment and

suspension (of atmospheric pollution)

Clear and transparent, free of sediment and

suspension (of atmospheric pollution)

visual assessment

Acid value (mgKOH/g)

≯0.01

0.0008

IEC 62021-

1

Interfacial tension/(mN/m)

No general requirements

46

ISO 6295

Total sulfur content (mass fraction)/%

No general requirements

No general requirements

ISO 14596

corrosive sulfur

non-corrosive

non-corrosive

DIN 51353

Content of antioxidant additives (mass fraction)/percent

Oil with antioxidant additives (U)

≯0.08

0.042

IEC 60666

2-Furfural content/(mg/kg)

≯0.1

0.011

IEC 61198

Operational characteristics

Oxidation stability (120°C)

Test time: 332h

-

-

-

--Total acid value (in KOH)/(mg/g)

≯1.2

0.04

IEC 61125

Act C

--Oil sludge (mass fraction)/%

≯0.8

0.020

IEC 61125

Act C

--Dielectric loss factor (90°C)

≯0.500

0.004

IEC 60247

Gassing/(mm/min)

No general requirements

No general requirements

IEC 60628

Health Safety and Environmental Characteristics (HSE)

Flash point (closed)/°C

≮135

147.3

ISO 2719

PCA content (mass fraction)/%

≯3

0.8

BS 2000

Part 346

Polychlorinated biphenyl (PCB) content/(mass fraction)(mg/kg)

undetectable

undetectable

IEC 61619

1. Classification: Transformer oil

2. Executive Standard: GB 2536-2011 T-20 ℃ (general).

3. Storage conditions

(1) Temperature and humidity: The ambient temperature for storing transformer oil should be controlled between 1535 degrees Celsius and relative humidity between 45%65%. This can avoid the transformer oil being exposed to high temperature, high humidity and other adverse environments, so as to maintain its good performance.

(2) Ventilation: The storage location should be well ventilated to prevent evaporation and oxidation of the oil. Ventilation facilities should be of explosion-proof type to ensure safety.

(3) Fire prevention: the storage place should be far away from fire source, heat source and oxidant to prevent the transformer oil from burning or exploding due to heat.

4. Testing methods for transformer insulation oil

(1) Appearance inspection: including observing the color, odor, transparency, etc. of the oil.

(2) Physical property testing: including measuring the density, flash point, spontaneous ignition point, pour point, etc. of oil.

(3) Chemical composition testing: including measuring the acid value, neutralization value, water content, gas content, etc. of the oil.

(4) Electrical performance testing: including measuring the dielectric loss, dielectric constant, dielectric strength, etc. of the oil.


Own Factory

Cycloalkane Based Transformer Oil T-20


Employees at Working

Cycloalkane Based Transformer Oil T-20


Canned Oil Products

Cycloalkane Based Transformer Oil T-20


Transportation

Cycloalkane Based Transformer Oil T-20


SERVICE

Customer First

We always put customers first, listen to their needs, focus on their experience, and meet their diverse needs by providing personalized solutions.

Innovation Driven

We firmly believe that innovation is the core driving force for enterprise development. We encourage employees to propose innovative ideas, drive technological research and product upgrades, in order to maintain a competitive advantage.

 

FAQ:

Q:What are the advantages of your company compared to other companies?

A:Our company focuses on long-term goals and treats every client with integrity. We offer high quality construction techniques and materials to ensure the quality and longevity of your project. Although prices may be slightly higher than some companies, the quality of our services and the standard of our materials are also significantly higher than other companies.


Q:Why are your company's quotes so much higher than others?

A:Our company's quotes are based on comprehensive operating costs. Although the price may be slightly higher, our construction techniques and material quality standards are also higher. The high standard of workmanship and material quality is directly proportional to the price.


Q:Why can some companies offer a lot of discounts while your company cannot?

A:Our company focuses on providing high-quality services and products, rather than competing by lowering prices. Our prices are already very reasonable, and we do not offer so-called "discounts" by lowering the quality of our services.





 