Cycloalkane Based Transformer Oil I-10
This product can effectively prevent discharge phenomena and power loss under high voltage electric fields, and meet strict insulation performance requirements. It can effectively prevent discharge phenomena and power loss under high voltage electric fields, and meet strict insulation performance requirements. Good solubility, able to dissolve sludge formed during the operation of electrical equipment, avoiding damage to insulation materials and affecting heat transfer.
Product Details:Cycloalkane Based Transformer Oil I-10
I-10 transformer oil is a mineral oil or synthetic oil, typically composed of refined raw materials such as petroleum or natural gas. Through specific processing processes such as hydrogenation, desulfurization, and decolorization, impurities and harmful components can be removed, and its insulation and stability can be improved.
PARAMETER:
Sports Event | GB2536-2011 1-10°C (general purpose) Quality indicators | Typical properties | Test Methods |
Minimum Cold Commissioning Temperature (LCSET)/°C | -10 | - | - |
Functional characteristics | |||
Pour Point/°C | ≯-20 | -27 | GB/T 3535 |
Kinematic viscosity (40°C)/(mm²/s) | ≯12 | 9.4 | GB/T 265 |
Kinematic viscosity (-10°C)/(mm²/s) | ≯1800 | 145 | |
Water content/(mg/kg) | ≯30 | 19 | GB/T 7600 |
Breakdown voltage/kV Untreated oil | ≮ 0 | 68 | GB/T 507 |
Density (20°C)/(kg/m³) | ≯895 | 889.5 | SH/T 0604 |
Dielectric loss factor (90°C) | ≯0.005 | 0.0007 | GB/T 5654 |
Refining/stabilizing properties | |||
exterior condition | clear and transparent | clear and transparent | visual assessment |
Acid value (in KOH)/(mg/g) | ≯0.01 | <0.01 | NB/SH/T 0836 |
Water-soluble acids or bases | not have | not have | GB/T 259 |
Interfacial tension/(mN/m) | ≮40 | 44 | GB/T 6541 |
corrosive sulfur | non-corrosive | non-corrosive | SH/T0804 |
Antioxidant content (mass fraction) / % | 0.08~0.40 | 0.30 | NB/SH/T0802 |
2-Furfural content/(mg/kg) | ≯0.1 | <0.05 | NB/SH/T0812 |
Operational characteristics | |||
Oxidation stability (120°C) | - | - | NB/SH/T 0811 |
Test time: 500h | - | - | |
--Total acid value (in KOH)/(mg/g) | ≯1.2 | 0.20 | |
--Oil sludge (mass fraction)/% | ≯0.8 | 0.04 | |
--Dielectric loss factor (90°C) | ≯0.500 | 0.049 | GB/T 5654 |
HSE Characteristics | |||
Flash point (closed)/°C | ≮135 | 144 | GB/T 261 |
PCA content (mass fraction)/% | ≯3 | <3 | NB/SH/T 0838 |
Polychlorinated biphenyl (PCB) content/(mg/kg) | undetectable | not detected | SH/T 0803 |
1. Classification: Transformer oil
2. Executive Standard: GB 2536-2011 I-10 ℃ (general).
3. Application Scope: I-10 transformer oil is suitable for transformers with voltage levels of 220kV and below, as well as electrical equipment with similar requirements, and the operating environment needs to be above -10 ℃.
4. Performance requirements for transformer insulation oil:
(1) Flash point and self ignition point: Flash point refers to the lowest temperature at which insulating oil can burn under certain conditions, while self ignition point refers to the lowest temperature at which insulating oil can self burn under certain conditions. The higher the flash point and self ignition point, the higher the safety of the insulating oil.
(2) Dielectric loss: Dielectric loss refers to the electrical energy loss of insulating oil under the action of an electric field. The lower the dielectric loss, the better the insulation performance of the insulating oil.
Own Factory
Haikun, with a comprehensive office, has an efficient management mechanism.
Employees at Working
Laboratory technicians at Haikun are experts in industrial oil oxidation resistance testing. Their professional judgment improves product quality.
Canned Oil Products
Haikun Petrochemical Technology Co., Ltd. has a proven packing system for sea - freight transportation. We use 200L iron containers and 20000L liquid bags, and ensure secure packing with appropriate supports during sea - freight shipping.
Transportation
With reliable transportation channels, Haikun Petrochemical is proficient in global sea shipping. We send insulating oils to various regions, including South America and Africa.
SERVICE
Service philosophy
Respect customers, products and services should be based on customer needs, and provide customers with better value choices for products and services.
To understand customers, one should research, design, and improve services from their perspective.
Power transmission and transformation services
We have built a complete industrial chain in the field of power transmission and transformation, including transformers, converter valves, switches, secondary equipment, cables, and casings.We provide turnkey engineering and system solutions for more than 30 countries, including survey, design, construction, installation, commissioning, training, operation, and maintenance.
FAQ:
1. Which port can you ship the cargo ?
SHANGHAI,TIANJIN,QINGDAO or others.
2. Do you accept product customization?
Yes of course. Please provide specific drawings or parameters we will quote you after evaluation.
3. Can you provide sample ?
Small samples in store and can provide the samples for free.Customized samples will take about 5-7days.