Cycloalkane Based Transformer Oil
Manufactured from highly refined lubricant base oils with the addition of antioxidants, insulating oils serve as crucial dielectrics in electrical equipment. Their primary characteristics are their ability to operate at low temperatures, strong oxidative resistance, and minimal dielectric losses. Low-temperature performance refers to the oil's natural convection, heat dissipation, and instant arc current interruption in electrical devices at low temperatures. Hence, they must possess a low pour point and low viscosity under such conditions.
Product Details:Cycloalkane Based Transformer Oil
As a fractionated product of petroleum refining, transformer oil is a carefully formulated blend of alkanes, cycloalkanes, and aromatic hydrocarbons, originating from natural crude oil. Its core functions encompass insulation and cooling of transformers and associated electrical equipment, efficiently transferring heat away from the system to facilitate cooling. This critical role helps stabilize transformer temperatures, forestalling overheating issues, and ultimately safeguarding the continuity and safety of production processes.
PARAMETER:
Sports Event | GB2536-2011 1-10°C (general purpose) Quality indicators | Typical properties | Test Methods |
Minimum Cold Commissioning Temperature (LCSET)/°C | -10 | - | - |
Functional characteristics | |||
Pour Point/°C | ≯-20 | -27 | GB/T 3535 |
Kinematic viscosity (40°C)/(mm²/s) | ≯12 | 9.4 | GB/T 265 |
Kinematic viscosity (-10°C)/(mm²/s) | ≯1800 | 145 | |
Water content/(mg/kg) | ≯30 | 19 | GB/T 7600 |
Breakdown voltage/kV Untreated oil | ≮ 0 | 68 | GB/T 507 |
Density (20°C)/(kg/m³) | ≯895 | 889.5 | SH/T 0604 |
Dielectric loss factor (90°C) | ≯0.005 | 0.0007 | GB/T 5654 |
Refining/stabilizing properties | |||
exterior condition | clear and transparent | clear and transparent | visual assessment |
Acid value (in KOH)/(mg/g) | ≯0.01 | <0.01 | NB/SH/T 0836 |
Water-soluble acids or bases | not have | not have | GB/T 259 |
Interfacial tension/(mN/m) | ≮40 | 44 | GB/T 6541 |
corrosive sulfur | non-corrosive | non-corrosive | SH/T0804 |
Antioxidant content (mass fraction) / % | 0.08~0.40 | 0.30 | NB/SH/T0802 |
2-Furfural content/(mg/kg) | ≯0.1 | <0.05 | NB/SH/T0812 |
Operational characteristics | |||
Oxidation stability (120°C) | - | - | NB/SH/T 0811 |
Test time: 500h | - | - | |
--Total acid value (in KOH)/(mg/g) | ≯1.2 | 0.20 | |
--Oil sludge (mass fraction)/% | ≯0.8 | 0.04 | |
--Dielectric loss factor (90°C) | ≯0.500 | 0.049 | GB/T 5654 |
HSE Characteristics | |||
Flash point (closed)/°C | ≮135 | 144 | GB/T 261 |
PCA content (mass fraction)/% | ≯3 | <3 | NB/SH/T 0838 |
Polychlorinated biphenyl (PCB) content/(mg/kg) | undetectable | not detected | SH/T 0803 |
1. Oil Change Procedure
Transformer oil replacement is a crucial maintenance task requiring meticulous preparation. First, the transformer's de-energization and isolation are confirmed to ensure operational safety. Following this, the old oil is drained thoroughly, and the interior of the oil tank is cleaned comprehensively. The new oil is infused slowly through specialized piping and an oil filter, with close attention paid to oil level changes. After the oil change, electrical tests and oil quality analysis are performed to verify transformer performance and new oil quality. Finally, the oil change process is documented for future maintenance reference.
2. Electrical Performance Testing
The Dielectric Dissipation Factor serves as a metric reflecting the extent of energy loss in transformer oil within an electric field, offering insights into the oil's electrical performance and potential contamination or aging issues.
The Breakdown Voltage assessment determines the transformer oil's capability to withstand electrical stress thresholds. A low breakdown voltage signifies increased vulnerability to electrical breakdown, potentially disrupting equipment operations.
Resistivity measurements gauge the conductivity of transformer oil, with compliant oil exhibiting resistivity within prescribed limits, vital for maintaining power equipment's seamless functioning.
Own Factory
Employees at Working
Canned Oil Products
Transportation
Enterprise Culture
By embracing teamwork, we multiply our power. Here, individuals operate not as soloists but as cohesive units, working hand in hand. We promote seamless collaboration across departments, erasing boundaries, pooling our assets, and jointly overcoming challenges. It is this collective synergy that allows us to swiftly react and achieve success amidst complexities.