In the realm of electrical equipment, insulating oil can be oxidized over time by heat and oxygen when subjected to an electric field. Oils fortified with antioxidants and metal passivators show enhanced oxidative stability. It is generally expected that the dielectric loss of transformer oil at 90℃ remains under 0.5%. This dielectric loss serves as an indicator of the oil’s performance in an AC electric field, often expressed as the tangent of the dielectric loss angle (δ). Naphthenic oil is favored for electrical appliance oils due to its low pour point, good fluidity at low temperatures, and excellent electrical and thermal characteristics.
Product Details:Dielectric Fluid Solutions
Insulating oils possess a comprehensive set of advantages, including high dielectric capability, elevated flash points, low viscosity levels, freedom from organic acids, alkalis, and sulfur corrosion, effective prevention of emulsification, minimal residue formation during regular use, rapid settling of arc byproducts, and a low pour point. These qualities render them ideally suited for their vital insulating and cooling roles in electrical installations.
PARAMETER:
Sports Event | Quality Indicators | measured value | Test Methods |
Functional characteristics | |||
Pour Point/°C | -40 | -48.3 | ISO 3016 |
Kinematic viscosity (40℃)/(m㎡/s) | ≯12 | 9.46 | ISO 3104 |
Kinematic viscosity (-10°C)/(mm²/s) | ≯1800 | 1028 | ISO 3104 |
Water content/(mg/kg) | ≯30/40 | 8.6 | IEC 60814 |
Breakdown voltage/kV (untreated oil) | ≮30 | 63.7 | IEC 60156 |
Density (20°C)/(g/ml) | ≯895 | 886 | ISO 12185 |
Dielectric loss factor (90°C) | ≯0.005 | 0.00047 | IEC 60247 |
Refining/stabilizing properties | |||
exterior condition | Clear and transparent, free of sediment and suspension (of atmospheric pollution) | Clear and transparent, free of sediment and suspension (of atmospheric pollution) | visual assessment |
Acid value (mgKOH/g) | ≯0.01 | 0.0008 | IEC 62021- 1 |
Interfacial tension/(mN/m) | No general requirements | 45.3 | ISO 6295 |
Total sulfur content (mass fraction)/% | No general requirements | No general requirements | ISO 14596 |
corrosive sulfur | non-corrosive | non-corrosive | DIN 51353 |
Content of antioxidant additives (mass fraction)/percent Oil with antioxidant additives (U) | ≯0.08 | 0.063 | IEC 60666 |
2-Furfural content/(mg/kg) | ≯0.1 | 0.011 | IEC 61198 |
Operational characteristics | |||
Oxidation stability (120°C) Test time: 332h | - | - | - |
--Total acid value (in KOH)/(mg/g) | ≯1.2 | 0.04 | IEC 61125 Act C |
--Oil sludge (mass fraction)/% | ≯0.8 | 0.020 | IEC 61125 Act C |
--Dielectric loss factor (90°C) | ≯0.500 | 0.004 | IEC 60247 |
Gassing/(mm/min) | No general requirements | No general requirements | IEC 60628 |
Health Safety and Environmental Characteristics (HSE) | |||
Flash point (closed)/°C | ≮135 | 148.2 | ISO 2719 |
PCA content (mass fraction)/% | ≯3 | 0.8 | BS 2000 Part 346 |
Polychlorinated biphenyl (PCB) content/(mass fraction)(mg/kg) | undetectable | undetectable | IEC 61619 |
1. Factors Affecting Service Life
Transformer Load: High loads on a transformer over extended periods can lead to faster oil aging, resulting in a shorter operational life. Therefore, careful control of the transformer load is essential for prolonging the oil's lifespan.
Oil Quality: The longevity of transformer oil is significantly influenced by its quality. Highquality oil offers better thermal stability and resistance to aging, which can extend its service life. On the other hand, lowquality oil may degrade rapidly, resulting in a shorter lifespan.
2. Oil Change Inspection
Chromatography: Chromatography allows for the detection of dissolved gases in the oil, such as hydrogen, methane, and ethane. The presence of these gases may indicate the presence of overheating, discharge or other abnormalities within the transformer, and may also indicate aging or contamination of the oil.
Standards and Specifications: Refer to national or industry standards for transformer oil quality. If test results fall below these standards, transformer oil replacement may be required.
Own Factory
Employees at Working
Canned Oil Products
Transportation
Enterprise Culture
The unwavering drive towards excellence guides our every step. Unsatisfied with the status quo, we embrace the future, challenging ourselves to push beyond limits and attain new heights of excellence. Through a commitment to process optimization, efficiency enhancement, and product innovation, we strive to become the industry's preeminent force, leading the charge towards fresh developments and trends.
Customer Testimonials
"The industrial lubricating oil from Haikun is a real treasure. It's efficient, long-lasting, and comes with a factory warranty. Plus, the packaging is excellent. – South Korea, Jae Lee"