Natural Ester Transformer Oil For Transformers U-10
Transformer oil exhibits remarkable thermal stability, significantly reducing the internal temperature of equipment during long-term operation, thus preserving its operational integrity. During extended use, electrical equipment generates substantial internal heat. Transformer oil, acting as a coolant, efficiently circulates to dissipate this heat through the radiator, enabling the equipment to maintain its optimal operating temperature.
Product Details:Natural Ester Transformer Oil For Transformers U-10
Prevent corrosion and oxidation: This oil can also protect metal surfaces from corrosion and prevent oil from reacting with other materials and forming harmful substances. In addition, it can also prevent oil from oxidizing at high temperatures and losing its insulation performance and stability.
PARAMETER:
Sports Event | IEC60296:2020 TVBUs (LCSET-30°C) Quality indicators | Typical properties | Test Methods |
Functional characteristics | |||
Pour Point/°C | ≯-20 | -25 | ISO 3016 |
Kinematic viscosity (40°C)/(mm²/s) | ≯12 | 11.5 | ISO 3104 |
Kinematic viscosity (-30°C)/(mm²/s) | ≯1800 | 1400 | |
Water content/(mg/kg) | ≯30 | 18 | IEC 60814 |
Breakdown voltage/kV | - | - | IEC 60156 |
-Untreated oil | ≮30 | 40-70 | |
-Treated oil | ≮70 | >70 | |
Density (20°C)/(kg/m³) | ≯895 | 889 | ISO 12185 |
Dielectric loss factor (90°C) | ≯0.005 | <0.001 | IEC 60247 |
Refining/stabilizing properties | |||
saturation (color theory) | ≯1.5 | 0.5 | ISO 2049 |
exterior condition | Clear and transparent, no precipitation | Clear and transparent, no precipitation | visual assessment |
Acid value/(mgKOH/g) | ≯0.01 | <0.01 | IEC 62021-1 |
Interfacial tension/(mN/m) | ≮40 | 46 | ASTMD 971 |
corrosive sulfur | non-corrosive | non-corrosive | DIN 51353 |
corrosive sulfur | - | non-corrosive | ASTMD 1275B |
Potentially corrosive sulfur | non-corrosive | non-corrosive | IEC62535 |
DBDS/(mg/kg) | Not detectable (<5) | not detected | IEC 62697-1 |
Antioxidant content/% | Not detectable (<0.01) | not detected | IEC 60666 |
Metal passivator/(mgkg) | Not detectable (<5) | not detected | IEC 60666 |
2-Furfural content and related substances (single component) (mg/kg) | Not detectable (<0.05) | <0.01 | IEC 61198 |
Operational characteristics | |||
Chlorine stability (164h) | - | - | IEC 61125 |
--Total acid value (mg KOH/g) | ≯1.2 | 0.70 | |
-- Oil sludge/% | ≯0.8 | 0.35 | |
--Dielectric loss factor (90°C) | ≯0.500 | 0.040 | IEC 60247 |
HSE Characteristics | |||
Flash point (closed)/°C | ≮135 | 145 | ISO 2719 |
PCA content/% | <3 | <3 | IP 346 |
Polychlorinated biphenyl (PCB) content/(mg/kg) | undetectable | undetectable | IEC 61619 |
Classification: Transformer oil
Executive Standard: GB 2536-2011 U-10 ℃ (general).
Application Scope: U-10 transformer oil is suitable for transformers and electrical equipment with similar requirements that users require oil without antioxidants.
Performance requirements for transformer insulation oil:
1.Flash point and self ignition point: Flash point refers to the lowest temperature at which insulating oil can burn under certain conditions, while self ignition point refers to the lowest temperature at which insulating oil can self burn under certain conditions. The higher the flash point and self ignition point, the higher the safety of the insulating oil.
2. Corrosion resistance: Corrosion resistance refers to the ability of insulating oil to corrode the internal metal components of transformers. The better the corrosion resistance, the longer the service life of the transformer.
Own Factory
Employees at Working
Canned Oil Products
Transportation
SERVICE
Service philosophy
Respect customers, products and services should be based on customer needs, and provide customers with better value choices for products and services.
To understand customers, one should research, design, and improve services from their perspective.
Power transmission and transformation services
We have built a complete industrial chain in the field of power transmission and transformation, including transformers, converter valves, switches, secondary equipment, cables, and casings.We provide turnkey engineering and system solutions for more than 30 countries, including survey, design, construction, installation, commissioning, training, operation, and maintenance.
FAQ:
Q: Who are we?
A:Our production location is in Shandong Province, China, mainly producing high-quality transformer oil, vacuum oil filters, and transformers. We have business segments in Nordic, African, South American, Middle Eastern and other regions.
Q:What are your terms of payment?
A:T/T 50% when signed contract, T/T 30% when goods are ready, T/T balance 20% before shipping out the goods.
Q: What are the advantages of your company ?
A:We have many professionals, technical personnel, more competitive prices and best after-dales service.