Hydroprocessed Naphthenic Transformer Fluid
Transformer oil, a necessary insulating medium for electrical equipment, is largely extracted and refined from petroleum, with alkanes and cycloalkanes being its primary components. With excellent electrical insulation properties, it can efficiently isolate the high-voltage parts within the transformer, thus stopping leakage and short circuits. Due to its good thermal conductivity, it can rapidly carry away the heat produced during the transformer's operation, preventing overheating and damage. It also has some arc-extinguishing capability, quickly extinguishing the arc when the switching device interrupts the current and forms an arc.
Product Details:Hydroprocessed Naphthenic Transformer Fluid
In the power grid, the transformer is an essential piece of equipment. The normal operation of the transformer is key to the safety of the entire power grid system, and the performance of the transformer oil directly impacts the reliability of the transformer's operation. Consequently, we have to perform well in the selection, application, and management of transformer oil to ensure the secure operation of the transformer. When it comes to the selection criteria, first and foremost, the performance of the oil needs to be considered. Its quality must meet the requirements determined by factors including the voltage level of the equipment and the ambient temperature of the location. Besides, the compatibility between the oil and other related insulating materials must also be taken into account.
Parameter:
Sports Event | Quality Indicators | measured value | Test Methods |
Functional characteristics | |||
Pour Point/°C | -50 | -57.5 | ISO 3016 |
Kinematic viscosity (40℃)/(m㎡/s) | ≯12 | 9.52 | ISO 3104 |
Kinematic viscosity (-10°C)/(mm²/s) | ≯1800 | 1028 | ISO 3104 |
Water content/(mg/kg) | ≯30/40 | 9.0 | IEC 60814 |
Breakdown voltage/kV (untreated oil) | ≮30 | 64.5 | IEC 60156 |
Density (20°C)/(g/ml) | ≯895 | 886 | ISO 12185 |
Dielectric loss factor (90°C) | ≯0.005 | 0.0005 | IEC 60247 |
Refining/stabilizing properties | |||
exterior condition | Clear and transparent, free of sediment and suspension (of atmospheric pollution) | Clear and transparent, free of sediment and suspension (of atmospheric pollution) | visual assessment |
Acid value (mgKOH/g) | ≯0.01 | 0.0008 | IEC 62021- 1 |
Interfacial tension/(mN/m) | No general requirements | 45.3 | ISO 6295 |
Total sulfur content (mass fraction)/% | No general requirements | No general requirements | ISO 14596 |
corrosive sulfur | non-corrosive | non-corrosive | DIN 51353 |
Content of antioxidant additives (mass fraction)/percent Oil with antioxidant additives (U) | ≯0.08 | 0.065 | IEC 60666 |
2-Furfural content/(mg/kg) | ≯0.1 | 0.012 | IEC 61198 |
Operational characteristics | |||
Oxidation stability (120°C) Test time: 332h | - | - | - |
--Total acid value (in KOH)/(mg/g) | ≯1.2 | 0.04 | IEC 61125 Act C |
--Oil sludge (mass fraction)/% | ≯0.8 | 0.020 | IEC 61125 Act C |
--Dielectric loss factor (90°C) | ≯0.500 | 0.004 | IEC 60247 |
Gassing/(mm/min) | No general requirements | No general requirements | IEC 60628 |
Health Safety and Environmental Characteristics (HSE) | |||
Flash point (closed)/°C | ≮135 | 148.2 | ISO 2719 |
PCA content (mass fraction)/% | ≯3 | 0.8 | BS 2000 Part 346 |
Polychlorinated biphenyl (PCB) content/(mass fraction)(mg/kg) | undetectable | undetectable | IEC 61619 |
1. Applicable Industry
Industrial motors: Transformer oil is utilized in high-power motors for insulation and cooling, helping to prevent overheating and ensuring that the motor operates efficiently.
Generators: In the context of generators, transformer oils assist in maintaining consistent operating temperatures and reducing the chances of equipment failure.
Communications Equipment: In military-grade communications devices, transformer oil provides both insulation and cooling, ensuring reliability in environments characterized by high temperatures and vibrations.
Avionics: Within avionics systems, transformer oils are employed to provide insulation and dissipate heat, ensuring that equipment functions correctly at high altitudes and in severe weather conditions.
2. Factors Affecting Service Life
To maintain the longevity of transformer oil, it is essential to conduct regular quality analysis and testing. The testing process includes evaluating insulation resistance, absorption ratio, polarization index, dielectric loss, winding leakage current, and the presence of microwater in the oil. By thoroughly analyzing these results, one can identify issues such as moisture content, impurities, or aging. If problems are detected, an initial step can be to attempt oil regeneration through filtration for continued use. However, if filtration does not resolve the issue or if the oil quality has significantly declined, replacing the transformer oil with a new supply becomes necessary.
Own Factory
Haikun, with 4 50 - square - meter oil tanks, manages its oil inventory effectively.
Employees at Working
Our team at Haikun is full of energy in the industrial oil field. Everyone works hard and has fun while achieving business goals.
Canned Oil Products
Haikun Petrochemical Technology Co., Ltd. has mastered the packing for sea - freight logistics. We use 200L steel containers and 20000L flexitanks for safe delivery of oils.
Transportation
Haikun Petrochemical Technology Co., Ltd. has a stable shipping network. We're experienced in sea freight, sending transformer oils to South America, Africa, and Russia.
Enterprise Culture
We follow the "customer - focused" business model. We attach great importance to customers' needs. Through detailed study of customer requirements, we keep upgrading our products and services, striving to be remarkable in the intense market contest and gain customers' affection.
Customer Testimonials
Transformer oil from Haikun is really satisfying. They focus on customer satisfaction and product quality. The parameters are spot - on, and the assay is reliable. The sales service was great. - Russia, Voronov Dmitry