Cycloalkane Based Transformer Oil I-20

Transformer oil is a fractionation product of petroleum, mainly composed of alkanes, cycloalkanes saturated hydrocarbons, aromatic unsaturated hydrocarbons and other compounds, which is a kind of mineral oil obtained from natural petroleum through distillation and refining. It is mainly used for insulation and cooling of transformers and electric equipment. It has good heat conduction properties, which can effectively transfer the heat inside the transformer and play a role in cooling the machine. Transformer oil helps to keep the temperature of the transformer stable, preventing failures caused by overheating and ensuring the safety of the production process.


Product Details

Product Details:Cycloalkane Based Transformer Oil I-20

As a fractionated product of petroleum refining, transformer oil is a carefully formulated blend of alkanes, cycloalkanes, and aromatic hydrocarbons, originating from natural crude oil. Its core functions encompass insulation and cooling of transformers and associated electrical equipment, efficiently transferring heat away from the system to facilitate cooling. This critical role helps stabilize transformer temperatures, forestalling overheating issues, and ultimately safeguarding the continuity and safety of production processes.


 Cycloalkane Based Transformer Oil I-20

 

PARAMETER

Sports Event

GB2536-2011

1-10°C (general purpose) Quality indicators

Typical properties

Test Methods

Minimum Cold Commissioning Temperature (LCSET)/°C

-10

-

-

Functional characteristics

Pour Point/°C

≯-20

-27

GB/T 3535

Kinematic viscosity (40°C)/(mm²/s)

≯12

9.4

GB/T 265

Kinematic viscosity (-10°C)/(mm²/s)

≯1800

145

Water content/(mg/kg)

≯30

19

GB/T 7600

Breakdown voltage/kV Untreated oil

0

68

GB/T 507

Density (20°C)/(kg/m³)

≯895

889.5

SH/T 0604

Dielectric loss factor (90°C)

≯0.005

0.0007

GB/T 5654

Refining/stabilizing properties

exterior condition

clear and transparent

clear and transparent

visual assessment

Acid value (in KOH)/(mg/g)

≯0.01

<0.01

NB/SH/T 0836

Water-soluble acids or bases

not have

not have

GB/T 259

Interfacial tension/(mN/m)

≮40

44

GB/T 6541

corrosive sulfur

non-corrosive

non-corrosive

SH/T0804

Antioxidant content (mass fraction) / %

0.08~0.40

0.30

NB/SH/T0802

2-Furfural content/(mg/kg)

≯0.1

<0.05

NB/SH/T0812

Operational characteristics

Oxidation stability (120°C)

-

-

NB/SH/T 0811

Test time: 500h

-

-

--Total acid value (in KOH)/(mg/g)

≯1.2

0.20

--Oil sludge (mass fraction)/%

≯0.8

0.04

--Dielectric loss factor (90°C)

≯0.500

0.049

GB/T 5654

HSE Characteristics

Flash point (closed)/°C

≮135

144

GB/T 261

PCA content (mass fraction)/%

≯3

<3

NB/SH/T 0838

Polychlorinated biphenyl (PCB) content/(mg/kg)

undetectable

not detected

SH/T 0803

 

1. Oil Change Procedure

Before replacing transformer oil, a thorough inspection of the transformer's condition is necessary to ensure it's de-energized and the old oil is drained. Subsequently, the interior of the oil tank is cleaned to prevent residue of impurities. The infused new slowly oil while undergoes monitoring filtration oil through level an and oil temperature pur.ifier to remove moisture and particles. During replacement, the new oil is Upon completion, oil quality tests are conducted, and the transformer's operation is observed to ensure a successful oil change.


2. New Equipment Test

Acceptance of the new transformer oil injected into the electrical equipment, because it is in contact with solid insulating materials and structural materials dissolved in a number of impurities, so that its performance changes, with the performance of the oil is not used to make a difference in the performance of the degree of change in its performance with the type of equipment and the selection of insulating materials and different differences. Therefore, before the equipment is put into operation, the oil quality inspection should be carried out to GB/T 7595 “put into operation before the oil” quality control standards, the equipment can be put into operation.

 

Own Factory

Cycloalkane Based Transformer Oil I-20


Employees at Working

Cycloalkane Based Transformer Oil I-20


Canned Oil Products

Cycloalkane Based Transformer Oil I-20


Transportation

Cycloalkane Based Transformer Oil I-20

 


Enterprise Culture

Our corporate culture is rooted in honesty, which we consider paramount. We firmly believe that treating people sincerely is the cornerstone for fostering long-term trust and collaboration. In our business transactions, we prioritize clear communication, steadfast commitment to our promises, and translating our words into meaningful actions, adhering to the philosophy of 'deeds that match words, success that stems from effort,' to collectively create a landscape of integrity in business.

 

Customer Testimonials

"As a manufacturer in Kazakhstan, we've tried several suppliers for our industrial lubricant needs. Haikun Petrochemical stands out for their exceptional product quality and swift delivery. Their team's knowledge of the industry is invaluable, and we're grateful for their partnership." — Kazakhstan, Aliya Nurmaganbetov


Leave your messages

Related Products

x

Popular products

x