Flame-Retardant Transformer Insulation
Designed specifically for electrical equipment such as transformers, transformer oil is commonly made from mineral or synthetic oils and boasts two critical characteristics. One is its outstanding insulating properties, which allow it to function as an insulating barrier in electrical equipment, safely isolating components in high-voltage settings and stopping current leakage. The other is its good heat dissipation ability, which can promptly carry away heat produced by equipment operation, keeping the equipment running stably and guaranteeing the reliable and efficient operation of the power system.
Product Details:Flame-Retardant Transformer Insulation
This product adopts a deep hydrogenation methodology, resulting in sulfur content <0.001% and aromatic hydrocarbons <5%—metrics that align with all EU environmental requirements. More than 95% of it can be recovered and reused. Notably, to match the compact nature of urban power grid equipment, it enhances liquidity to improve heat dissipation efficiency. This extension of equipment lifespan by 30% or more allows the product to effectively combine performance, environmental sustainability, and adaptability to various application contexts.
Parameter:
Sports Event | Quality Indicators | Measured value | Test Methods |
Functional characteristics | |||
Pour Point/°C | -50 | -57.5 | ISO 3016 |
Kinematic viscosity (40℃)/(m㎡/s) | ≯12 | 9.52 | ISO 3104 |
Kinematic viscosity (-10°C)/(mm²/s) | ≯1800 | 1028 | ISO 3104 |
Water content/(mg/kg) | ≯30/40 | 9.0 | IEC 60814 |
Breakdown voltage/kV (untreated oil) | ≮30 | 64.5 | IEC 60156 |
Density (20°C)/(g/ml) | ≯895 | 886 | ISO 12185 |
Dielectric loss factor (90°C) | ≯0.005 | 0.0005 | IEC 60247 |
Refining/stabilizing properties | |||
Exterior condition | Clear and transparent, free of sediment and suspension (of atmospheric pollution) | Clear and transparent, free of sediment and suspension (of atmospheric pollution) | Visual assessment |
Acid value (mgKOH/g) | ≯0.01 | 0.0008 | IEC 62021- 1 |
Interfacial tension/(mN/m) | No general requirements | 45.3 | ISO 6295 |
Total sulfur content (mass fraction)/% | No general requirements | No general requirements | ISO 14596 |
Corrosive sulfur | non-corrosive | non-corrosive | DIN 51353 |
Content of antioxidant additives (mass fraction)/percent Oil with antioxidant additives (U) | ≯0.08 | 0.065 | IEC 60666 |
2-Furfural content/(mg/kg) | ≯0.1 | 0.012 | IEC 61198 |
Operational characteristics | |||
Oxidation stability (120°C) Test time: 332h | - | - | - |
--Total acid value (in KOH)/(mg/g) | ≯1.2 | 0.04 | IEC 61125 Act C |
--Oil sludge (mass fraction)/% | ≯0.8 | 0.020 | IEC 61125 Act C |
--Dielectric loss factor (90°C) | ≯0.500 | 0.004 | IEC 60247 |
Gassing/(mm/min) | No general requirements | No general requirements | IEC 60628 |
Health Safety and Environmental Characteristics (HSE) | |||
Flash point (closed)/°C | ≮135 | 148.2 | ISO 2719 |
PCA content (mass fraction)/% | ≯3 | 0.8 | BS 2000 Part 346 |
Polychlorinated biphenyl (PCB) content/(mass fraction)(mg/kg) | undetectable | undetectable | IEC 61619 |
1. Oil Change Inspection
Check for Appearance: Assess the oil for any visible impurities or deposits, which may result from aging, oxidation, or contamination. A noticeable dark or cloudy appearance could indicate that the oil needs to be replaced.
Conduct Insulation Resistance Tests: An insulation resistance test should be performed, as a decline in resistance can indicate moisture or other contaminants in the oil, potentially affecting its insulating effectiveness.
2. Factors Affecting Service Life
To ensure the longevity of transformer oil, it is crucial to perform regular quality testing and analysis. This should include evaluations of insulation resistance, absorption ratio, polarization index, dielectric loss, winding leakage current, and microwater content in the oil. A thorough examination of these factors allows for the identification of moisture, impurities, or signs of aging. If problems are detected, an initial solution may be to regenerate the oil through filtration. However, if this approach is impractical or if the oil quality has significantly worsened, it will be necessary to replace the transformer oil entirely.
Own Factory
Haikun, with 10 20 - square - meter finished products tanks, stores products safely.
Employees at Working
Our team at Haikun is passionate about the industrial oil business. Everyone enjoys their work and contributes to the company's progress.
Canned Oil Products
Haikun Petrochemical Technology Co., Ltd. has a proven packing system for sea - freight transportation. We use 200L iron containers and 20000L liquid bags, and ensure secure packing with appropriate supports during sea - freight shipping.
Transportation
We at Haikun Petrochemical are pros at sea freight. Our reliable channels ship insulating oils to various countries, including those in South America and Africa.
Enterprise Culture
We strongly hold the belief that details determine whether one will succeed or fail. During our work process, we take note of every single detail and aim for excellence. This continuous pursuit of details has led to our products and services winning broad acclaim from our customers.
Customer Testimonials
Haikun Petrochemical's industrial lubricants are amazing. They understand customers and provide products with precise parameters. The purchase process was smooth. - South Asia, Verma Ramesh
In the corners of substations and the arteries of power grids, our transformer oil flows silently. It won’t make the soil weep if it leaks, nor will it leave residues that keep groundwater restless—and there’s no trace of PCB hiding within. From urban centers to rural villages, from industrial plants to wild landscapes, it protects every patch of land it touches, thanks to its inherent green qualities.