Insulating Oil For Transformers I-10
1.Excellent electrical insulation performance, with high breakdown voltage and low dielectric loss factor.
2.Good thermal stability and oxidative stability, can prevent the formation of acids and sludge during use, prolonging the service life of electrical equipment and reducing maintenance costs.
3.Does not contain corrosive sulfides such as DBDS, which can prevent the deposition of copper sulfide (CuS) on insulating paper and reduce electrical insulation performance, thereby reducing the risk of equipment failures.
1.Product Details
I-10 transformer oil is formulated by blending moderately refined cycloalkyl base oil with high-quality antioxidant additives, featuring fast heat transfer, good oxidative stability, and excellent electrical performance.The product has stable and reliable performance.
Classification: Transformer oil
Executive Standard: GB 2536-2011 I-10 ℃ (general).
Application Scope: I-10 transformer oil is suitable for transformers with voltage levels of 220kV and below, as well as electrical equipment with similar requirements, and the operating environment needs to be above -10 ℃.
2.Parameter
Sports Event | GB2536-2011 1-10°C (general purpose) Quality indicators | Typical properties | Test Methods |
Minimum Cold Commissioning Temperature (LCSET)/°C | -10 | - | - |
Functional characteristics | |||
Pour Point/°C | ≯-20 | -27 | GB/T 3535 |
Kinematic viscosity (40°C)/(mm²/s) | ≯12 | 9.4 | GB/T 265 |
Kinematic viscosity (-10°C)/(mm²/s) | ≯1800 | 145 | |
Water content/(mg/kg) | ≯30 | 19 | GB/T 7600 |
Breakdown voltage/kV Untreated oil | ≮ 0 | 68 | GB/T 507 |
Density (20°C)/(kg/m³) | ≯895 | 889.5 | SH/T 0604 |
Dielectric loss factor (90°C) | ≯0.005 | 0.0007 | GB/T 5654 |
Refining/stabilizing properties | |||
exterior condition | clear and transparent | clear and transparent | visual assessment |
Acid value (in KOH)/(mg/g) | ≯0.01 | <0.01 | NB/SH/T 0836 |
Water-soluble acids or bases | not have | not have | GB/T 259 |
Interfacial tension/(mN/m) | ≮40 | 44 | GB/T 6541 |
corrosive sulfur | non-corrosive | non-corrosive | SH/T0804 |
Antioxidant content (mass fraction) / % | 0.08~0.40 | 0.30 | NB/SH/T0802 |
2-Furfural content/(mg/kg) | ≯0.1 | <0.05 | NB/SH/T0812 |
Operational characteristics | |||
Oxidation stability (120°C) | - | - | NB/SH/T 0811 |
Test time: 500h | - | - | |
--Total acid value (in KOH)/(mg/g) | ≯1.2 | 0.20 | |
--Oil sludge (mass fraction)/% | ≯0.8 | 0.04 | |
--Dielectric loss factor (90°C) | ≯0.500 | 0.049 | GB/T 5654 |
HSE Characteristics | |||
Flash point (closed)/°C | ≮135 | 144 | GB/T 261 |
PCA content (mass fraction)/% | ≯3 | <3 | NB/SH/T 0838 |
Polychlorinated biphenyl (PCB) content/(mg/kg) | undetectable | not detected | SH/T 0803 |
Own Factory
Employees at Working
Canned Oil Products
Transportation
Service
Technical advantages
The production line utilizes ABB's intelligent automation online blending technology (ILB), renowned globally for its power and automation solutions. Additionally, it incorporates McPhell's Swiss-made vacuum filtration device.
Power transmission and transformation services
We have established a comprehensive industrial chain in the realm of power transmission and transformation, encompassing transformers, converter valves, switches, secondary equipment, cables, and casings. Our products find extensive application in sectors such as power grids, power generation, new energy, high-speed rail, subway systems, petroleum and petrochemical industries, large-scale data centers, transportation networks, urban infrastructure development, intelligent manufacturing, and 5G technology.
We offer turnkey engineering and system solutions to over 30 countries, covering surveying, design, construction, installation, commissioning, training, operation, and maintenance services.
Q&A
Q: What is transformer oil?
A: Transformer oil is a mineral oil or synthetic oil, typically composed of refined raw materials such as petroleum or natural gas. Through specific processing processes such as hydrogenation, desulfurization, and decolorization, impurities and harmful components can be removed, and its insulation and stability can be improved.